Fuel, Oil and Coolant Analysis for Backup Generators

Generators are critical in applications where power continuity is essential for safety, security, operations, and/or data integrity. Following are some vital applications that rely heavily on generators:

• Hospitals & Healthcare Facilities: Lives depend on uninterrupted power for ventilators, surgical equipment, medication refrigeration, and lighting during surgeries or emergencies.
• Data Centers: Data loss or server downtime can cost thousands to millions of dollars per minute.
• Emergency Services (Police, Fire, EMS): These services must respond instantly—communications, dispatch systems, and lighting must stay live.
• Industrial and Manufacturing Plants: Sudden outages can cause equipment damage, product loss, or safety hazards in processes involving high heat, pressure, or chemicals.
• Commercial Buildings (especially high-rises): Elevators, emergency lighting, fire alarms, and security systems must work during outages.
• Utilities and Water Treatment Facilities: Water supply, sewage systems, and grid infrastructure must remain operational to avoid health and safety crises.
• Retail and Food Storage: Spoiled inventory, security issues, and customer service interruptions can result from outages.
• Schools & Universities: Student safety, security systems, and remote learning platforms depend on reliable power.
• Airports and Transportation Hubs: Power is needed for air traffic control, runway lights, passenger safety, and much more.

Regular testing of the fuel, lubricant, and coolant in generators is essential to ensure reliable performance, prevent unexpected breakdowns, and extend equipment life. Here’s why each matters.

FUEL TESTING
Fuel testing is crucial for maintaining generator reliability and performance. Stored fuel is susceptible to contamination from water, microbes, and particulates, which can clog filters, corrode components, and reduce efficiency. High-quality fuel ensures proper combustion, improving power output and minimizing emissions. Regular testing also helps detect degradation or incompatible fuel. Testing leads to reduced wear on injectors and engine parts, extending equipment life and lowering maintenance costs. Additionally, it supports compliance with environmental regulations by verifying related metrics such as sulfur content. Following are recommended tests.

• Karl Fischer Water Content: Detects water that can cause microbial growth, rust, and injector damage.
• Microbial Contamination (Bacteria/Fungi): Identifies biological growth that forms sludge and biofilm in fuel tanks.
• Particle Count: Measures solid debris that can clog filters and damage injectors.
• Fuel Stability: Checks for fuel degradation over time, especially in stored diesel.
• Flash Point: Ensures safety by measuring volatility and ignition characteristics.
• Cetane Number: Indicates ignition quality—important for cold starts and smooth running.
• Sulfur Content: Verifies compliance with ultra-low sulfur diesel regulations.
• Viscosity: Ensures proper fuel processing and injector performance.

OIL TESTING
The oil in generators needs to be tested regularly to ensure the engine operates efficiently and reliably. Over time, oil degrades due to heat, contamination, and oxidation, which can lead to increased wear, corrosion, and even engine failure if left unchecked. Regular oil testing helps detect early signs of problems, such as contamination; buildup of soot or metal particles; and changes in essential properties such as viscosity. Recommended oil tests for generators include:
• Viscosity: Ensures the oil maintains proper thickness for lubrication.
• Acid Number (AN)/Base Number (BN): Measures oil acidity or its ability to neutralize acids, indicating oil degradation or remaining life.
• Fuel Dilution: Identifies unburned fuel contamination that can reduce lubrication and cause damage.
• Water Content: Indicates potential coolant leaks or condensation issues that can cause rust or corrosion.
• Oxidation: Measures oxidation due to heat exposure, which can affect oil performance.
• Particle Count: Especially useful in high-performance or critical power systems, this test checks oil cleanliness and helps prevent abrasive wear.
• Elemental Spectroscopy: Measures the amount of key elements related to wear, additives and contaminants.

These tests can be done as part of a preventive maintenance program and are especially critical for backup generators that may sit idle for long periods but need to perform instantly when required.

COOLANT TESTING
Analysis of the coolant is essential to achieve optimum generator performance and longevity. Coolant can be compromised by combustion gases, oil, or debris--leading to overheating or component wear. Following are recommended Coolant Tests for generators:
• pH Level: Indicates acidity or alkalinity; a drop in pH can lead to corrosion of metal components.
• Freeze Point: Confirms that the coolant concentration is adequate to prevent freezing in cold conditions.
• Boiling Point: Ensures the coolant won’t evaporate or boil over under high-temperature operation.
• Nitrite, Molybdate, and Other Additives: Tests the levels of corrosion inhibitors; low levels indicate that the coolant is no longer protective.
• Chloride and Sulfate Contamination: Detects water or air ingress that can cause corrosion or pitting.
• Glycol Concentration: Measures the glycol-to-water ratio, critical for heat transfer and freeze protection.
• Total Dissolved Solids (TDS): Measures the accumulation of debris, corrosion products, and scale-forming materials.
• Visual Inspection: Helps identify oil contamination, discoloration, or particulate matter at a glance.

These tests are vital for both diesel and gas-powered generators, particularly those that run in demanding environments or serve as critical backup systems. Regular coolant analysis helps extend engine life, reduce maintenance costs, and ensure generator readiness. 
Together, regular fuel, oil, and coolant testing form a predictive maintenance strategy that reduces costly repairs and ensures the generator is always available. 
For more information on working with Eurofins TestOil for oil analysis programs or training opportunities, fill out the form below; visit https://testoil.com/company/contact-us/; call 216-251-2510; or email sales@testoil.com.

About Eurofins TestOil
With more than 30 years of experience in the oil analysis industry, Eurofins TestOil focuses exclusively on assisting industrial facilities with reducing maintenance costs and avoiding unexpected downtime through oil and fuel analysis program implementation. As industry experts in diagnosing oil-related issues in equipment such as turbines, hydraulics, gearboxes, pumps, compressors and diesel generators, Eurofins TestOil provides customers with same-day turnaround on routine oil analysis testing. For more information on partnering with Eurofins TestOil on oil analysis programs or training opportunities visit https://testoil.com. Contact: Al Yates 216-251-2510; sales@testoil.com.

About Eurofins – the global leader in bio-analysis
Eurofins is Testing for Life. Eurofins is the global leader in food, environment, pharmaceutical and cosmetic product testing, and in discovery pharmacology, forensics, advanced material sciences and agroscience Contract Research services. Eurofins is also a market leader in certain testing and laboratory services for genomics, and in the support of clinical studies, as well as in BioPharma Contract Development and Manufacturing. The Group also has a rapidly developing presence in highly specialised and molecular clinical diagnostic testing and in-vitro diagnostic products.
With over 61,000 staff across a network of 940 laboratories in 59 countries, Eurofins’ companies offer a portfolio of over 200,000 analytical methods. Eurofins Shares are listed on Euronext Paris Stock Exchange.

Comments are closed.